Power conversion · PCS

From DC to the grid,
in both directions.

Bidirectional power conversion systems charge the battery from the grid or from solar and return the energy as grid-quality AC. In an AC integrated system the PCS ships inside the container. A DC block takes its conversion separately: modular string PCS, or a complete APEX MV skid.

215kWString PCS module
99%Peak efficiency, 215 kW
<3%THDi at rated power
−1…+1Power factor
<10msIsland transfer
01 · Where conversion sits

Inside the container,
or beside it.

The battery is the same in both. What differs is where its DC is turned into AC, and that sets the voltage at which a system meets your site.

One container · A1000 / A2000 PCS125 kW × n 400 V AC Site LV boardor transformer
AC integrated · A1000, A2000The PCS ships in the box.Racks and 125 kW converter modules share one enclosure and one controller. The system leaves the factory as a 400 V AC source. AC integrated systems →
DC block · A3000 – A6250 1 500 VDC String PCSor APEX skid215 kW × n AC GridLV or MV
DC block · A3000 – A6250The PCS is sized to the connection.The block delivers up to 1 500 V DC. String PCS or an APEX skid converts it, so the plant’s power is set by the grid offer, not by the container. DC blocks →
02 · PCS modules

Two module families.
One controller.

Conversion is built from modules that parallel to the rating the duty needs. A module fault costs one module of capacity and minutes of technician time, not a crane and a shutdown. Both families answer to Solaris™.

AC integratedInside A1000 · A2000
125kW

The converter module inside the AC integrated systems. Modules parallel onto the container’s 400 V output and are commissioned with the battery as one tested unit.

Rating
125 kW per module
In the A1000
4 × 125 kW = 500 kW
In the A2000
8 × = 1 000 kW, or 4 × = 500 kW
DC side
728 – 936 V832 V nominal battery cluster
AC output
400 V 3P4W
Grid modes
On-grid · off-grid · hybrid
String PCSFor DC blocks · APEX
215kW

One bidirectional converter per battery string at up to 1 500 V DC. Modules parallel into groups and the groups onto a 690 V bus, at low voltage or on an APEX skid.

DC voltage
1 000 – 1 500 V
DC input
206 A per module
AC side
690 V · 50 / 60 Hz ± 5 Hz
Peak efficiency
Up to 99 %
Grid support
VSG control, grid-forming capable
Operating modes
CC · CP · MPPT · AC or DC voltage source
03 · Pairing

A converter for
every block.

Every battery system has a matched converter. The AC integrated systems carry theirs inside; each DC block pairs with string PCS or an MV skid, sized to the duty rather than rounded up to the nearest catalogue item.

SystemEnergyConverter at 2 hConfigurationGrid interface
AC integrated systems · PCS inside
A10001.00 MWh500 kW4 × 125 kW, integrated400 V 3P4W
A20002.00 MWh1 000 kW8 × 125 kW, integrated (500 kW build: 4 ×)400 V 3P4W
DC blocks · conversion supplied separately
A30003.00 MWh1 500 kW215 kW string PCSLV or MV
A40004.00 MWh2 000 kW215 kW string PCS11 / 22 kV via MV skid
A50005.00 MWh2 500 kW12 × 215 kW, two groups10–35 kV via APEX X2500
A62506.25 MWh3 125 kW215 kW string PCS11 / 22 / 33 kV via MV skid
Modular

Built from modules

Hot-swappable conversion modules parallel to the rating you need. A module fault costs one block of capacity and minutes of technician time — not a crane and a shutdown.

Four-quadrant

Real and reactive

Full P/Q control across the capability curve, power factor adjustable −1 to +1, THDi below 3% at rated power. Reactive support available even when the battery is idle.

Grid-forming

Islanding & black start

Grid-forming firmware provides synthetic inertia and voltage support on weak networks, with sub-10 ms transfer to island mode and battery-led black start where required.

04 · Grid interface

Where the plant
meets the network.

Grid code

NRS 097-2-1 interface

The point of connection is the utility’s; the interface is ours: grid-code studies, reactive capability, ride-through and the connection application, to NRS 097-2-1 and the SA grid connection code.

−1…+1Power factor
<3%THDi
MV SKID · APEX X2500

Medium-voltage power skid

Twelve 215 kW converters, an oil-immersed step-up and fused MV switching on one 20 ft skid at 10 – 35 kV. Factory-integrated and tested before dispatch, so site work is placement and terminations. The APEX →

10–35kVMV output
2 500kWRated AC
STS

Transfer & islanding

Integrated static transfer switch for sites that must ride through a network event. Sub-10 ms transfer to island mode, with battery-led black start where the site has no other source.

<10msTransfer
YesBlack start
05 · Specification

Conversion at a glance.

Conversion & grid
Grid modesOn-grid / off-grid / hybrid
Transfer time (STS)< 10 ms
Power factor−1 to +1, four-quadrant
Current distortionTHDi < 3% at rated power
LV output400 V 3P4W (AC integrated) · 690 V (string PCS)
MV output10 – 35 kV via APEX X2500 or MV skid
CommunicationRS-485 / CAN / Ethernet · Solaris™ EMS
215 kW PCS module · tested to
SafetyEN 62109 · IEC 62477
EMCEN IEC 61000 · EN 62920
South AfricaNRS 097-2-1
EuropeEN 50549-1 / -2 · VDE-AR-N 4110 · NC RfG
United KingdomG99 · G100
OtherIEC 61727 · IEC 62116 · FD C11-519-12 · SunSpec

Certificates apply to the 215 kW PCS module. Final ratings and the protection scheme are fixed in the project technical agreement.